BS EN 50600-2-2:2014
$167.15
Information technology. Data centre facilities and infrastructures – Power distribution
Published By | Publication Date | Number of Pages |
BSI | 2014 | 40 |
This European Standard addresses power supplies to, and power distribution within, data centres based upon the criteria and classifications for āavailabilityā, āphysical securityā and āenergy efficiency enablementā within EN 50600-1.
This European Standard specifies requirements and recommendations for the following:
-
power supplies to data centres;
-
power distribution systems within data centres;
-
facilities for both normal and emergency lighting;
-
equipotential bonding and earthing;
-
lightning protection;
-
devices for the measurement of the power consumption characteristics at points along the power distribution system and their integration within management tools.
Safety and electromagnetic compatibility (EMC) requirements are outside the scope of this European Standard and are covered by other standards and regulations. However, information given in this European Standard may be of assistance in meeting these standards and regulations.
Conformance of data centres to the present document is covered in Clause 4.
PDF Catalog
PDF Pages | PDF Title |
---|---|
35 | AnnexĀ A (informative)Example implementations of power distribution A.1 Symbology A.2 Example implementations A.2.1 Class 1 power distribution A.2.2 Class 2 power distribution A.2.3 Class 3 power distribution A.2.4 Class 4 power distribution |